You have to pick a transformer for a motor load. The motor draws 80 kW of real power and 60 kVAR of reactive power. A 80 kVA transformer is sitting on the shelf. Is it big enough? It is tempting to say yes, the load is 80 kW and the transformer is 80 kVA, done. Hold that thought before you order it.
The catch is that an AC load does not pull just one kind of power. Real power (kW) does the useful work: heat, torque, light. Reactive power (kVAR) does no net work, but it is what magnetizes the field inside motors and transformers so they can run. Both flow through the same wires, and the wire feels the combination, not just the part that does work.
Add them and you do not get 140. They sit at a right angle to each other, so you combine them like the legs of a right triangle. The apparent power (kVA) is the hypotenuse, and it is the total the conductor and transformer actually carry.
Run the numbers for our motor: square root of (80 squared plus 60 squared) is square root of 10,000, which is 100 kVA. That 80-60-100 is the old 3-4-5 right triangle. So the 80 kVA unit is too small. You need 100 kVA, because the transformer has to carry the apparent power, not the real power.
That is the whole reason a nameplate says kVA and not kW. The hardware is sized by the total current it carries, and that current is set by apparent power, kVAR included. The kW tells you what work gets done; the kVA tells you what the iron and copper have to survive.
Power factor penalties, reactive charges, and %Z mismatches show up as real line items on a utility bill or a bid rejection. DistroForge Insider applies these fundamentals to pricing and equipment-selection intelligence.