A qualified lineman pulls up to a 12.47 kV line with one bad cutout to swap. The job is energized, the crew is short, and a second truck is twenty minutes out. He is fully qualified, his gloves are tested, and the work is twenty minutes faster if he just climbs and does it solo. Before you read on, decide: is he allowed to do that work alone?
He is not. Under 1910.269, energized work on lines or equipment over 600 V requires a second qualified employee present. 12.47 kV is line-to-line voltage, far above that 600 V line. Being qualified does not change the answer. The rule keys off the voltage and the hazard, not the worker’s skill.
The reason is brutal and simple. When current crosses the chest it can stop the heart, and a person who stops breathing does not have long. Irreversible brain damage from oxygen loss starts at roughly 4 to 6 minutes. A solo worker who goes down at the top of a pole has no one to cut the source, lower him, and start CPR inside that window.
So the second qualified person is not there to hand up tools or fill out the job briefing. They are there for one job that nobody else on the planet can do fast enough: pull the victim clear, de-energize the line, and start compressions before that 4-minute clock runs out. The second person on an energized job exists to start CPR inside the survival window, nothing else. That is why the rule has no solo exception above 600 V, no matter how good the lineman is.